(2) How to recover from the parameter access error status
How to recover from the parameter access error status is as follows.
(a) Slave module hardware error
Eliminate the error cause by taking measures such as noise prevention. Then power off and on the
AnyWireASLINK system or turn on and off Error flag clear command (Yn0).
(b) Parameter access target module ID error, parameter value error
Eliminate the error cause such as a parameter access program. Then power off and on the AnyWireASLINK
system or turn on and off Error flag clear command (Yn0).
(c) Parameter access error
If any of the following errors has occurred, eliminate the error cause.
• Slave module hardware error (error code: 012C
• Slave module status error (error code: 0131
• Same ID used error (error code: 0190
When a parameter access error other than the above occurs, the possible cause is noise. Eliminate the error
cause by taking measures such as noise prevention. Then power off and on the AnyWireASLINK system or
turn on and off Error flag clear command (Yn0).
(d) Slave module status error
Check the status details of the target slave module to eliminate an error cause. Then power off and on the
AnyWireASLINK system or turn on and off Error flag clear command (Yn0).
The status details of the slave module can be checked with the AnyWireASLINK parameter in Parameter
storage area 1 (Un\G12288 to Un\G12335).
*1
Buffer memory address when one slave module is connected. For details, refer to Page 109, Appendix 2 (15).
(e) Same ID used error, no ID setting error
Eliminate the error cause such as Same ID used error. Then power off and on the AnyWireASLINK system or
turn on and off Error flag clear command (Yn0).
After recovery from parameter access error status, the following status is resulted:
Slave module hardware error
Parameter access target module ID
error
Parameter value error
Slave module status error
Same ID used error
No ID setting error
Parameter access error
66
Type
• Slave module alarm signal (X(n+1)0) turns off.
• The data in Latest error code storage area (Un\G10256) is cleared.
• The data in Latest error ID storage area (Un\G10257) is cleared.
• The data in Number of the alarm IDs (Un\G9984) is cleared.
• The data in Alarm ID information storage area (Un\G9985 to Un\G10112) is cleared.
• Parameter access error (X(n+1)2) turns off.
• The data in Latest error code storage area (Un\G10256) is cleared.
• The data in Latest error ID storage area (Un\G10257) is cleared.
• The data in Number of the error IDs (Un\G8192) is cleared.
• The data in Error ID information storage area (Un\G8193 to Un\G8320) is cleared.