3.6 Alarms Configuration

Overview.
Four alarms per channel – identified A1 to D1 (for channel 1) up to A4 to D4 (for channel 4).
High/Low process alarms.
Fast/Slow rate alarms.
Adjustable hysteresis value – prevents oscillation of alarm state.
Time hysteresis – enables delayed triggering of alarms.
Process
Variable
High Process
Low Process
Fig. 3.1 High and Low Process Alarm with Hysteresis
Output
0
Time in seconds
Counter
Started
Example shows time hysteresis set to 70 seconds used with a high process alarm
Fig. 3.2 Time Hysteresis Alarm
IM/C1300 Rev. J
40
0
Counter
Counter
Reset
Started
Time Hysteresis Status
70
130
Hysteresis Time
Counter
Elapsed
Reset
3 Configuration
Hysteresis
Trip Point
Hysteresis
Alarm On
Alarm Off
Alarm On
Alarm Off
Alarm Trip Point
Alarm On
Alarm Off
31