ABB C1300 User Manual page 29

Advanced circular chart recorder
Hide thumbs Also See for C1300:
Table of Contents

Advertisement

C1300
Advanced circular chart recorder
Input Type
set to
Thermocouple
or
RTD
Input Type
Millivolts
Milliamps
Resistance (High)
Resistance (Low)
Volts
Table 3.1 Limits of Electrical Ranges
IM/C1300 Rev. J
Channel Units
Select any of the units pre-programmed into the recorder or select 113 Custom and the
and
keys to enter the units required – see Fig. 2.1 on page 6.
Notes.
Any characters not permitted in user-defined units are skipped when scrolling through the
selection.
Refer to Appendix B on page 78 for a description of the units pre-programmed into the
recorder.
Electrical Input Range High
Set the maximum electrical input value required, within the limits shown in Table 3.1.
Electrical Input Range Low
Set the minimum electrical input value required, within the limits shown in Table 3.1.
Decimal Point
Select the decimal point position for the engineering and chart ranges.
Continued on next page.
Electrical Range Low
0
0
0
0
0
Electrical Range High
150
50
9999
750
5
3 Configuration
Minimum Span (Low to High)
5.0
1.0
400
20
0.1
,
27