Chapter 10
Functions
10:55 Start ramp, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Start Ramp1
This parameter makes it possible to set the start ramp time for the first parameter set.
Parameter text
Start Ramp1
10:56 Initial voltage, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Init Volt1
This parameter makes it possible to set the initial voltage for the first parameter set.
Parameter text
Init Volt1
10:57 Current limit, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./Curr Lim1
This parameter makes it possible to set the current limit level for the first parameter set.
Parameter text
Curr Lim1
10:58 Setting current, first sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/1st Seq. Param./1st Set Ie
This parameter makes it possible to set the rated motor current for the first parameter set.
Parameter text
1st Set Ie
10:59 Start ramp, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Start Ramp2
This parameter makes it possible to set the start ramp time for the second parameter set.
Parameter text
Start Ramp2
10:60 Initial voltage, second sequence
Path in menu:
Menu/SETTINGS/Functional Settings/
Seq Start/2nd Seq. Param./Init Volt2
This parameter makes it possible to set the initial voltage for the second parameter set.
Parameter text
Init Volt2
Default value
Setting range
Description
10 s
1...30s, 1...120s
First sequence, time for start ramp
Default value
Setting range
Description
30%
30...70%
First sequence, initial voltage for start ramp
Default value
Setting range
Description
4 x Ie
2.0...7.0xle
First sequence, current limit
Default value
Setting range
9...1207A divided into 19 over-
Ir
lapping ranges
Default value
Setting range
Description
10s
1...30s, 1...120s
Second sequence, time for start ramp
Default value
Setting range
Description
30%
30...70%
Second sequence, initial voltage for start ramp
Description
First sequence, current limit
Low Voltage Products & Systems