Top level

Settings
Figure 10: Application setting menu

Application Setting

Select
Figure 11: Application setting menu
Centrifugal Pump
Store Set
Back
Figure 12: Application type
Centrifugal Pump
Next
Back
Figure 13: Confirming application type
Setting Ie
100A
Store
Figure 14: Setting Ie menu
Setting Ie
100A
Next
Back
Figure 15: Confirming Setting Ie
OL Class
Store
Figure 16: Overload class
OL Class
Next
Figure 17: Confirming OL Class
Ext ByPass
Store
Figure 18: External By-Pass
Ext ByPass
Next
Figure 19: Confirming External By-Pass
Ready?
Yes
Tune Set
Figure 20: Ready?/Tune Set menu
Low Voltage Products & Systems
ABB nc. • 888-385-1221 • www.abb-control.com
Chapter 7
Settings and configuration
7:2.2 Application Setting
The Application setting menu consists of predefined parameters for the selected applica-
Application setting
tion and should be used if an easy and quick set-up is required. Only a few parameters

Basic settings

need to be set to allow the start of the motor. All necessary input data will show up in an
automatic loop.

Functional settings

Enter the Application setting

Presentation settings

Enter the menu by selecting Application Setting.

Service settings

Select what type of application the softstarter is used for by pressing Store Set. If the

All settings

desired application is not listed, select the one closest to the application and choose Tune

Changed settings

Set (see below). Possible applications are:

Reset all settings

• Centrifugal Pump
• Hydraulic Pump
Operation mode
• Centrifugal Fan
• Axial Fan
• Compressor
• Conveyor
• Crusher
• Mixer
• Bow Thruster
Confirm the selected application by pressing Next. If the wrong application type was
selected, press Back and select the correct type.
Setting I
Set the motor full load current (i.e. rated motor current if the unit is connected In Line).
For units connected Inside Delta, the Setting I
delta circuit = 58% (1/( 3)) of the rated motor current.
Press Store to save the data after setting the current.
10
Confirm the Setting I
correct value.
Overload class (OL Class)
Select the desired overload class. Available classes:
10
• 10A
Back
• 10
• 20
• 30
Press Store to save the selected class.
Yes
Confirm the selected overload class by pressing Next. If the wrong overload class was
selected, press Back and select the correct class.
External By-Pass contactor (Ext ByPass)
Yes
If an External Bypass contactor is used, set the parameter to Yes, otherwise select No.
Back
Press Store to save the data.
Confirm the selection of external by-pass by pressing Next. If the wrong selection was
made, press Back and correct the selection.
Tune Set
The configuration of the application setting menu is now complete. If no tuning of the set-
tings is desired, it is possible to return to the top level by pressing Yes.
If tuning some parameters is desired, select Tune Set.
(motor FLA)
e
by pressing Next. If the wrong value is set, press Back and set the
e
must be set according to the current in the
e
1SXU 132 021 M0201
7