Low Voltage Products & Systems
ABB nc. • 888-385-1221 • www.abb-control.com
Chapter 7
Settings and configuration
7:1.1 Overview of all accessible settings (different menus) cont.
Description
Setting current
Time for start ramp
Time for stop ramp
Initial voltage for start ramp
End voltage for stop ramp
Step down voltage
Level of the current limit
Selection of kick start
Level of kick start
Time for kick start
Range for start ramp
Range for stop ramp
Overload protection
Overload class
Overload class, Dual type, Start class
Overload class, Dual type, Run class
Type of operation for overload protection
Locked rotor protection
Trip level for locked rotor protection
Trip time for locked rotor protection
Type of operation for locked rotor protection
Underload protection
Trip level for underload protection
Trip time for underload protection
Type of operation for underload protection
Phase imbalance protection
Trip level for phase imbalance protection
Type of operation for imbalance protection
High current protection
Type of operation for high current protection
Phase reversal protection
Type of operation for phase reversal protection
PTC protection
Type of operation for PTC protection
Use of external by-pass contactor
Type of operation, by-pass doesn't open
Type of operation, by-pass doesn't close
High current warning
Trip level for high current warning
Low current warning
Trip level for low current warning
Motor overload warning
Trip level for motor overload warning
Thyristor overload warning
Type of operation for phase loss fault
Type of operation for fieldbus fault
Type of operation for frequency fault
Type of operation for heatsink overtemp fault
Type of operation for shorted thyristor fault
Function of programmable input In0
Display
Setting
text
range
Setting Ie
9.0...1207A
Start Ramp
1...30s, 1...120s
Stop Ramp
0...30s, 0...120s
Init Volt
30...70%
End Volt
30...70%
Step down
30...100%
Current Lim
2.0...7.0xle
Kick Start
Yes, No
Kick Level
50...100%
Kick Time
0.1...1.5s
Start Range
1-30s, 1-120s
Stop Range
0-30s, 0-120s
Overload
No, Normal, Dual
OL Class
10A, 10, 20, 30
OL Class S
10A, 10, 20, 30
OL Class R
10A, 10, 20, 30
OL Op
Stop-M, Stop-A, Ind
Locked Rotor
Yes, No
Lock R Lev
0.5...8.0xle
Lock R Time
0.2...10s
Lock R Op
Stop-M, Stop-A, Ind
Underload
Yes, No
Underl Lev
0.4...0.8xle
Underl Time
1...30s
Underl Op
Stop-M, Stop-A, Ind
Phase Imb
Yes, No
Ph Imb Lev
10...80%
Ph Imb Op
Stop-M, Stop-A, Ind
High I
Yes, No
High I Op
Stop-M, Stop-A, Ind
Phase Rev
Yes, No
Ph Rev Op
Stop-M, Stop-A, Ind
PTC
Yes, No
PTC Op
Stop-M, Stop-A, Ind
Ext ByPass
Yes, No
BP Closed Op
Stop-M, Stop A
BP Open Op
Stop-M, Stop A
Warn I=High
Yes, No
Wa I=H Lev
0.5...5.0xle
Warn I=Low
Yes, No
Wa I=L Lev
0.4...1.0xle
Warn OL
Yes, No
Wa OL Lev
40...99%
Warn SCR OL
Yes, No
Ph Loss Op
Stop-M, Stop-A
FB Fault Op
Stop-M, Stop-A
Freq F Op
Stop-M, Stop-A
HS Temp Op
Stop-M, Stop-A
SCR SC Op
Stop-M, Stop-A
None, Reset,
In0
Enable Jog, DOL,
Start 2, FB-Dis
Default
Actual
value
setting
Individual
10s
0s
30%
30%
100%
4.0xle
No
50%
0.2s
1-30s
0-30s
Normal
10
10
10
Stop-M
No
4.0xle
1.0s
Stop-M
No
0.5xle
10s
Stop-M
No
80%
7
Stop-M
No
Stop-M
No
Stop-M
No
Stop-M
No
Stop-M
Stop-M
No
1.2xle
No
0.8xle
No
90%
No
Stop-M
Stop-M
Stop-M
Stop-M
Stop-M
Reset
7.5
1SXU 132 021 M0201