Chapter 10
Functions
10:43 Phase loss fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/Ph Loss Op
This parameter makes it possible to select between two different actions if a phase loss fault
occurs.
Parameter text
Ph Loss Op
10:44 Fieldbus fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/FB Fault Op
This parameter makes it possible to select between two different actions if a fault occurs in
the fieldbus communication.
Parameter text
FB Fault Op
10:45 Frequency fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/Freq F Op
This parameter makes it possible to select between two different actions if the frequency is
out of range (frequency fault).
Parameter text
Freq F Op
10:46 Heatsink over-temperature fault, type of operation
Path in menu:
Menu/SETTINGS/Functional Settings/
Faults/HS Temp Op
This parameter makes it possible to select between two different actions if the heat sink
temperature of the softstarter is too high.
Parameter text
HS Temp Op
Stop-M The motor stops and a manual reset is required before restart
Stop-A
The motor stops and an automatic reset is performed when the fault
disappears
Default value
Stop-M
Stop-M The motor stops and a manual reset is required before restart
Stop-A
The motor stops and an automatic reset is performed when the fault
disappears
Default value
Stop-M
Stop-M The motor stops and a manual reset is required before restart
Stop-A
The motor stops and an automatic reset is performed when the fault
disappears
Default value
Stop-M
Stop-M The motor stops and a manual reset is required before restart
Stop-A
The motor stops and an automatic reset is performed when the fault
disappears
Default value
Stop-M
Setting range
Description
Type of operation for
Stop-M, Stop-A
phase loss fault
Setting range
Description
Type of operation for
Stop-M, Stop-A
fieldbus fault
Setting range
Description
Type of operation for
Stop-M, Stop-A
frequency fault
Setting range
Description
Type of operation for
Stop-M, Stop-A
heat sink overtempera-
ture fault
Low Voltage Products & Systems
ABB Inc. • 888-385-1221 • www.abb-control.com