Ai111.0 Parameters - ABB UMC100.3 Manual

Univeral motor controller
Hide thumbs Also See for UMC100.3:
Table of Contents

Advertisement

PA R A M E T E R S A N D D ATA S T R U C T U R E S O N A F I E L D B U S

AI111.0 Parameters

Parameter
Parameter Name
Number
2
AI111 AM1 Enabled
3
AI111 AM2 Enabled
154
AM1 Tmax Delay
167
AM2 Tmax Delay
188 / 189 /
AM1 CH1/2/3 Err
190
Reac
182 / 183 /
AM1 Ch 1/2/3 Type
184
185 / 186 /
AM2 Ch 1/2/3 Type
187
174 / 175
AM1 / AM2 Mode
Description, Explanations
Specify if the module is connected to UMC
Specify if the module is connected to UMC
Delay in temperature mode before a trip is triggered
Delay in temperature mode before a trip is triggered
Define error reaction for a specific analog input channel
Define function of analog input channel
Define function of analog input channel
Operation mode of analog module
Options
0: Off
1: On
0: Off
1: On
0 ... 255 s in steps of 1s
0 ... 255 s in steps of 1s
Disabled (0), Trip (1), Warning (2)
Disabled (0)
PT100 -50°C...+400°C 2-wire (1)
PT100 -50°C...+400°C 3-wire (2)
PT100 -50°C...+70°C 2-wire (3)
PT100 -50°C...+70°C 3-wire (4)
PT1000 -50°C...+400°C 2-wire (5)
PT1000 -50°C...+400°C 3-wire (6)
KTY83 -50°C...+175°C (7)
KTY84 -40°C...+300°C (8)
NTC +80°C...+160°C (9)
0...10V (10)
0...20mA (11)
4...20mA (12)
Temperature (0)
Universal (1)
135
Adjustable via
All
All
All
All
All
All
All

Hide quick links: