Control Cable Ducts - ABB ACS800-07-0610-3 Hardware Manual

Acs800-07 series 500 to 2800 kw
Table of Contents

Advertisement

A diagram of the cable routing is below.
Input power cable

Control cable ducts

Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
90 °
min 200 mm (8 in.)
Control cables
24 V 230/120 V
Not allowed unless the 24 V
cable is insulated for 230/120 V
or insulated with insulation
sleeving for 230/120 V.
Motor cable
Drive
Power cable
Lead 24 V and 230/120 V control
cables in separate ducts inside
the cabinet.
min 300 mm (12 in.)
Motor cable
min 500 mm (20 in.)
24 V
230/120 V
Planning the electrical installation
69