Emergency Stop Input - ABB ACS800-07-0610-3 Hardware Manual

Acs800-07 series 500 to 2800 kw
Table of Contents

Advertisement

32

Emergency stop input

The DSSB board has a built-in logic that fulfils the emergency stop requirements
according to IEC/EN60204-1 / Category 0 (Immediate removal of power) provided
that:
• the Diode Supply Unit (DSU) is equipped with optional main contactors, and
• an emergency stop button is wired to the emergency stop input of the DSU. See
the figure below for connection to the DSSB board.
When the emergency stop is activated, the DSU stops and opens the main
contactors. Normal operation resumes after the emergency stop is deactivated and
the DSU is reset.
Note: Emergency stop according to category 0 and category 1 (controlled
emergency stop) are available as factory-installed options. The category 1 option
requires additional wirings that are not visible in the figure below. See the circuit
diagrams delivered with the unit for more information.
Hardware description
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Emergency stop button wired to DSSB board
DSSB board terminals
X4
1
-24V
2
+24V
3
Ground
X8
Emergency stop input
1
EM +24V 0: Emergency stop
2
EM -24V 0: Emergency stop
Note: The DSSB board terminals are wired to a separate terminal block to
which the user connections are made. See circuit diagrams delivered with the
unit.
Additional emergency stop buttons can be connected in series.
-24 VDC
+24 VDC
Ground