Requirements table

The following table shows how to select the motor insulation system and when an
optional ABB du/dt filter, insulated N-end (non-driven end) motor bearings and ABB
common mode filters are required. The motor manufacturer should be consulted
regarding the construction of the motor insulation and additional requirements for
explosion-safe (EX) motors. Failure of the motor to fulfil the following requirements
or improper installation may shorten motor life or damage the motor bearings.
Motor type
Nominal mains
voltage (AC line
voltage)
A
Random-
U
< 500 V
N
wound M2_
B
500 V < U
and M3_
B
600 V < U
Form-wound
380 V < U
HX_ and AM_
Old* form-
380 V < U
wound HX_
and modular
Random-
0 V < U
wound HX_
500 V < U
and AM_ **
N
Random-
U
< 420 V
N
wound and
O
form-wound
N
420 V < U
-
A
B
B
500 V < U
600 V < U
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Motor insulation
system
Standard
< 600 V Standard
N
or
Reinforced
< 690 V Reinforced
N
< 690 V Standard
N
< 690 V Check with the
N
motor
manufacturer.
< 500 V
Enamelled wire
N
with fibre glass
< 690 V
N
taping
Standard: Û
=
LL
1300 V
< 500 V Standard: Û
=
N
LL
1300 V
or
Reinforced: Û
LL
1600 V, 0.2 µs
rise time
< 600 V Reinforced: Û
N
LL
1600 V
or
Reinforced: Û
LL
1800 V
< 690 V Reinforced: Û
N
LL
1800 V
Reinforced: Û
LL
2000 V, 0.3 µs
rise time ***
Requirement for
ABB du/dt filter, insulated N-end bearing and ABB common mode
P
< 100 kW
100 kW < P
N
and
frame size < IEC 315
P
< 134 HP
134 HP < P
N
and frame size
< NEMA 500
-
+ N
+ du/dt
+ du/dt + N
-
+ N
+ du/dt
+ du/dt + N
n.a.
+ N + CMF
+ du/dt with voltages over 500 V + N + CMF
+ N + CMF
+ du/dt + N + CMF
-
+ N or CMF
+ du/dt
+ du/dt + N
or
+ du/dt + CMF
=
-
+ N or CMF
=
+ du/dt
+ du/dt + N
or
+ du/dt + CMF
=
-
+ N or CMF
=
+ du/dt
+ du/dt + N
=
-
N + CMF
filter
< 350 kW
P
N
or
frame size > IEC 315
frame size > IEC 400
< 469 HP
P
N
or frame size
or frame size
> NEMA 500
> NEMA 580
+ N + CMF
+ du/dt + N + CMF
+ N + CMF
+ du/dt + N + CMF
P
< 500 kW:
N
+ N + CMF
P
> 500 kW:
N
+ N + CMF + du/dt
+ N + CMF
+ du/dt + N + CMF
+ N + CMF
+ du/dt + N + CMF
+ N + CMF
+ du/dt + N + CMF
N + CMF
Planning the electrical installation
57
> 350 kW
N
or
> 469 HP
N

Hide quick links: