ABB ACS800-07-0610-3 Hardware Manual page 129

Acs800-07 series 500 to 2800 kw
Table of Contents

Advertisement

Input terminals at each
supply module (units without
load switch-disconnector or air
circuit breaker)
Input terminals (units with
load switch-disconnector or air
circuit breaker)
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Conductor size
Max. no. and size of cable
lugs per phase
IEC Cabling
2
< 150 mm
2 × 150 mm
2
185 ... 240 mm
OL 2 × 185-240 mm
dual-cable screw lug included
with delivery)
US Cabling
300 ... 350 MCM 2 × 350 MCM
Busbar dimensions
40 [1.57]
13 [0.51]
50 [1.97]
Number of input busbars (6-pulse units)
No. of supply modules
(n×D4)
1
2
3
4
Number of input busbars (12-pulse units)
No. of supply modules
(n×D4)
1
2
3
4
Lug hole
2
1 × 11
2
(with
2 × 1¾"
No. of
Bolt size
2)
busbars
M12 or
See below
½"
No. of busbars per connection point
1L1
1L2
1
1
2
2
3
3
3
3
No. of busbars per connection point
1L1
1L2
1L3
1
1
1
2
2
2
3
3
3
3
3
3
Bolt
Tightening
torque
M10
40 Nm
15 Nm
7/16"
30 lbf.ft
Tightening
torque
70 Nm
(50 lb.ft)
1L3
1
2
3
3
2L1
2L2
2L3
1
1
1
2
2
2
3
3
3
3
3
3
Technical data