DC fuses at inverter module input

U
U
U

Fuses for main circuit voltage measurement

Fuses F7 (2 pcs) and F8 (3 pcs) are used for DC voltage and AC supply voltage
measurement respectively. The recommended type for replacement is Ferraz
Shawmut A070GRB01T13 (1 A, 700 V, UL Recognized).

DC fuses for the DSU module

Each D4 type DSU module uses four fuses. The fuses are in two pairs, each pair
consisting of a 170M4417 (with a micro switch) and 170M4467 (with a red fuse
indicator) fuse connected in parallel.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Input
ACS800-
current
07... type
(A)
= 400 V (Range 380-415 V)
N
-0610-3
790
-0770-3
999
-0870-3
1128
-1030-3
1305
-1230-3
1591
-1540-3
1938
-1850-3
2394
= 500 V (Range 380-500 V)
N
-0760-5
793
-0910-5
944
-1090-5
1131
-1210-5
1233
-1540-5
1596
-1820-5
1831
-2310-5
2400
= 690 V (Range 525-690 V)
N
-0750-7
565
-0870-7
655
-1060-7
795
-1160-7
856
-1500-7
1131
-1740-7
1271
-2120-7
1595
-2320-7
1678
-2900-7
2086
-3190-7
2396
-3490-7
2490
Qty.
2
2
Qty.
Type (IEC)
4
170M8547
4
Bussmann
4
4
170M8550
6
Bussmann
6
8
4
170M8547
4
Bussmann
4
4
170M8550
6
Bussmann
6
8
4
170M8647
4
Bussmann
4
4
6
6
170M8650
8
Bussmann
8
10
12
12
Type
170M4417 Bussmann
170M4467 Bussmann
Rated
Type
current
(UL/CSA)
(A RMS)
170M6216
1250
Bussmann
170M6219
1600
Bussmann
170M6216
1250
Bussmann
170M6219
1600
Bussmann
170M8637
800
Bussmann
170M8639
1000
Bussmann
Rated current
(A RMS)
700
700
Technical data
121
Voltage (V)
690
690
690
690
1000
1000
Voltage (V)
690
690

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents