External Brake Chopper And Resistor(S) For The Acs800-31/U31 - ABB ACS800 Hardware Manual

Hide thumbs Also See for ACS800:
Table of Contents

Advertisement

124

External brake chopper and resistor(s) for the ACS800-31/U31

The nominal ratings for dimensioning the brake resistors for the ACS800-31 and
ACS800-U31 are given below at an ambient temperature of 40°C (104°F).
ACS800-31
Chopper
type
ACS800-U31
Type
type
Three-phase supply voltage 380 V, 400 V or 415 V
-0016-3
NBRA-653
SACE15RE22
-0020-3
NBRA-656
SACE15RE13
-0025-3
NBRA-656
SACE15RE13
-0030-3
NBRA-656
SAFUR90F575
-0040-3
NBRA-656
SAFUR90F575
-0050-3
NBRA-656
SAFUR90F575
-0060-3
NBRA-656
SAFUR80F500
-0070-3
NBRA-656
SAFUR125F500
-0100-3
NBRA-657
SAFUR125F500
Three-phase supply voltage 380 V, 400 V, 415 V, 440 V, 460 V, 480 V or 500 V
-0020-5
NBRA-653
SACE15RE22
-0025-5
NBRA-656
SACE15RE13
-0030-5
NBRA-656
SACE15RE13
-0040-5
NBRA-656
SAFUR90F575
-0050-5
NBRA-656
SAFUR90F575
-0060-5
NBRA-656
SAFUR90F575
-0070-5
NBRA-656
SAFUR80F500
-0100-5
NBRA-656
SAFUR80F500
-0120-5
NBRA-657
SAFUR125F500
R
Resistance value for the listed resistor assembly. Note: This is also the minimum allowed resistance for the brake resistor.
E
Short energy pulse that the resistor assembly withstands every 400 seconds. This energy will heat the resistor element from 40 °C
R
(104 °F) to the maximum allowable temperature.
P
Continuous power (heat) dissipation of the resistor when placed correctly. Energy E
Rcont
P
Maximum braking power of the drive equipped with the standard chopper and resistor. The drive and the chopper will withstand this
brmax
braking power for one minute every ten minutes. Note: The braking energy transmitted to the resistor during any period
shorter than 400 seconds may not exceed E
All braking choppers and resistors must be installed outside the converter module. Note: The SACE and SAFUR resistors are not UL
listed.
Resistor braking
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Brake resistor
R
E
P
R
Rcont
ohm
kJ
kW
22
420
2
13
435
2
13
435
2
8
1800
4.5
8
1800
4.5
8
1800
4.5
6
2400
6
4
3600
9
4
3600
9
22
420
2
13
435
2
13
435
2
8
1800
4.5
8
1800
4.5
8
1800
4.5
6
2400
6
6
2400
6
4
3600
9
.
R
Cable
P
brmax
No. of
elements
2
mm
kW
4
3x6+6
14.4
4
3x6+6
26.9
4
3x6+6
26.9
9
3x25+16
52.8
9
3x25+16
52.8
9
3x25+16
52.8
12
3x35+16
65.6
18
3x35+16
94.2
18
3x70+35
94.2
4
3x6+6
18.5
4
3x6+6
31.4
4
3x6+6
31.4
9
3x25+16
62.6
9
3x25+16
62.6
9
3x25+16
62.6
12
3x35+16
88.4
12
3x35+16
88.4
18
3x70+16
122.1
dissipates in 400 seconds.
R
Degree of protection
Chopper
Resistor
IP54
IP21
IP00
IP21
IP00
IP21
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP54
IP21
IP00
IP21
IP00
IP21
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
IP00
00184674 E