64
Frame sizes R6: Cable lug installation [16 to 70 mm
PE
6
Frame size R6: Screw terminal installation [95 to 185 mm
PE
6
Electrical installation
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
5
5
5
5
2
(6 to 2/0 AWG) cables]
Remove the screw terminals. Fasten the cable lugs
to the remaining bolts with M10 nuts.
Isolate the ends of
the cable lugs with
insulating tape or
shrink tubing.
Shroud on the conductor terminals (screw
terminal installation)
9
2
(3/0 to 350 AWG)] cables
b
a
a. Connect the cable to the terminal.
b. Connect the terminal to the drive.
WARNING! If the wire size is less than
2
95 mm
(3/0 AWG), a cable lug must
be used. A cable of wire size less than
2
95 mm
(3/0 AWG) connected to this
terminal will loosen and may damage
the drive.
9