Ground fault protection

The drive is equipped with an internal ground fault protective function to protect the
unit against ground faults in the motor and motor cable. This is not a personal safety
or a fire protection feature. The ground fault protective function can be disabled with
a parameter, refer to the appropriate ACS800 Firmware Manual.
The EMC filter of the drive includes capacitors connected between the main circuit
and the frame. These capacitors and long motor cables increase the ground leakage
current and may cause fault current circuit breakers to function.

Emergency stop devices

For safety reasons, install the emergency stop devices at each operator control
station and at other operating stations where emergency stop may be needed.
Note: Pressing the stop key (
an emergency stop of the motor or separate the drive from dangerous potential.

ACS800-02/U2 with enclosure extension and ACS800-07/U7

An emergency stop function is optionally available for stopping and switching off the
whole drive. Two stop categories according to IEC/EN 60204-1 (1997) are available:
immediate removal of power (Category 0 for ACS800-02/U2 and ACS800-07/U7)
and controlled emergency stop (Category 1 for ACS800-07/U7).

Restarting after an emergency stop

After an emergency stop, the emergency stop button must be released and the drive
started by turning the operating switch of the drive from position "ON" to "START".