2.5 TECHNICAL SPECIFICATIONS
Operating temperature:
Storage temperature:
Humidity (non condensing):
2
Altitude
Class of equipment
Equipment mobility
Overvoltage category
Pollution degree
Net weight:
Packaged:
Package dimensions:
CATEGORY
STANDARD
Dielectric voltage withstand
SAFETY
Dielectric voltage withstand
Insulation resistance
Electrostatic Discharge Immunity
Radiated RF Electromagnetic Field Immunity
Electrical Fast Transient Immunity
Surge Immunity
Conducted RF Immunity
Power magnetic Immunity
EMC
Power Frequency Immunity
Damped Oscillatory Wave Immunity
Voltage Dips & Interruptions
Ripple on DC
Radiated & Conducted Emissions
Sinusoidal Vibration
Shock & Bump
MECHANICAL
Seismic
Enclosure Protection
Cold test (storage)
Cold test (operational)
Dry heat test (storage)
CLIMATIC
Dry heat test (operational)
Change of Temperature
Damp Heat Humidity Cyclic
Damp Heat steady state
2-34
- 10°C to + 60°C
- 40°C to + 85°C
95%
Up to 2000 m
I
Fixed
III
2
5 kg
6 kg
30x40x40 cm (DxWxH)
CLASS
IEC60255-27
IEC60255-27
IEC60255-27
IEC60255-26/IEC61000-4-2
IEC60255-26/IEC61000-4-3
IEC60255-26/IEC61000-4-4
IEC60255-26/IEC61000-4-5
IEC60255-26/IEC61000-4-6
IEC60255-26/IEC61000-4-8
IEC60255-26/IEC61000-4-16
IEC60255-26/IEC61000-4-18
IEC60255-26/IEC61000-4-11/
IEC61000-4-29
IEC60255-26/IEC61000-4-17
IEC60255-26/CISPR11/
CISPR22
IEC60255-21-1
IEC60255-21-2
IEC60255-21-3
IEC60255-27/IEC60529
IEC60068-2-1
IEC60068-2-1
IEC60068-2-2
IEC60068-2-2
IEC60068-2-14
IEC60068-2-30
IEC60068-2-78
F650 Digital Bay Controller
2 PRODUCT DESCRIPTION
2.5.12 ENVIRONMENTAL CHARACTERISTICS
2.5.13 PACKAGING AND WEIGHT
2.5.14 TYPE TESTS
TEST
2 KV / 2.3 KV
5 KV
500 V (test level)
Level 4
Level 3
Zone A
Zone A
Level 3
Level 5
Zone A
2.5 KV Common Mode 1 KV Diff. Mode
Levels based on IEC61000-4-11 &
IEC61000-4-29
15% Rated DC value
Class A
Class 1
Class 1
Class 2
IP52
-40˚C 16 hrs
-20˚C 16 hrs
85˚C 16 hrs
60˚C 16 hrs
5 cycles (3+3) -20˚C/60˚C
6 cycles (12+12) 55˚C @ 93% R.H.
40˚C @ 93% R.H.
GEK-113000AE