<location>Topology: Actual topology contains SINUMERIK and SIMOTION
components
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
The detected actual topology contains SINUMERIK and SIMOTION components.
The drive system is no longer booted. In this state, the drive control (closed-loop) cannot be enabled.
Alarm value (r2124, interpret hexadecimal):
ddccbbaa hex: cc = fault cause, bb = component class of the actual topology, aa = component number of the compo-
nent
cc = 01 hex = 1 dec:
An NX10 or NX15 was connected to a SIMOTION control.
cc = 02 hex = 2 dec:
A CX32 was connected to a SINUMERIK control.
Remedy:
Re alarm value = 1:
Replace all NX10 or NX15 by a CX32.
Re alarm value = 2:
Replace all CX32 by an NX10 or NX15.
201362
<location>Topology: Topology rule(s) broken
Message value:
%1
Drive object:
All objects
Reaction:
NONE
Acknowledge:
NONE
Cause:
At least one topology rule for the SINAMICS S120 Combi has been broken.
In the event of a fault, the ramping up of the drive system is aborted and closed-loop drive control is not enabled.
Fault value (r0949, interpret decimal):
The fault value indicates which rule has been broken.
1: The S120 Combi may only be wired via DRIVE-CLiQ socket X200 to X1 on the NCU.
2: Only one Terminal Module 54F (TM54F) may be connected to DRIVE-CLiQ socket X2 on the NCU. If a TM54 is
being used, it may only be wired via X500 to X2 on the NCU.
3: Only one DRIVE-CLiQ Hub Module (hub) may be connected to DRIVE-CLiQ socket X3 on the NCU. If a hub is being
used, it may only be wired via X500 to X3 on the NCU.
4: Only Sensor Modules may be connected to DRIVE-CLiQ sockets X201 through X203 (3-axis) or X204 (4-axis) on
the S120 Combi.
5: Only one Single Motor Module or one Double Motor Module may be connected to DRIVE-CLiQ socket X205 (X204
is not available for 3-axis). The module must be wired to the S120 Combi via X200.
6: Only certain Motor Modules may be used for expansion axes.
7: If a Single Motor Module is being used as the first expansion axis, only one more Single Motor Module may be con-
nected (via X200 to X201 on the first Single Motor Module).
8: Only Sensor Modules may be connected to the corresponding DRIVE-CLiQ socket X202 on any Single Motor Mod-
ules which may be present.
9. On the second Single Motor Module there must be nothing connected to X201.
10: If a Double Motor Module is used as an expansion axis, only Sensor Modules may be connected to X202 and X203.
11: On the Double Motor Module there must be nothing connected to X201.
12: On the Terminal Module 54F (TM54F) there must be nothing connected to X501.
13: On the DRIVE-CLiQ Hub Module, only Sensor Modules Cabinet (SMC) and Sensor Modules External (SME) may
be connected to X501 through X505.
Remedy:
Evaluate the fault value and ensure compliance with the corresponding topology rule(s).
Alarms
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
SINAMICS alarms