Block %2 Axis %3 Is Not An Indexing Axis; Block %2 Indexing Axis %3 With Hirth Tool System Is Active - Siemens Sinamics S120 Diagnostic Manual

Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

NCK alarms
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Modify NC program: Assign the value of the machine data or of the system variable to a program-local variable and
transfer this as parameter.
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
17500
[Channel %1: ] Block %2 axis %3 is not an indexing axis
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Axis name, spindle number
Definitions:
An indexing axis position has been programmed for an axis with the keywords CIC, CAC or CDC that has not been
defined as indexing axis in the machine data.
Reaction:
Correction block is reorganized.
Interface signals are set.
Alarm display.
Remedy:
Please inform the authorized personnel/service department. Remove programming instruction for indexing axis posi-
tions (CIC, CAC, CDC) from the NC part program or declare the relevant axis to be an indexing axis.
Indexing axis declaration:
Modify MD30500: $MA_INDEX_AX_ASSIGN_POS_TAB (indexing axis assignment)
The axis will become an indexing axis when an assignment to an indexing position table was made in the stated MD.
2 tables are possible (input value 1 or 2).
Modify MD10900 $MN_INDEX_AX_LENGTH_POS_TAB_1
Modify MD10920 $MN_INDEX_AX_LENGTH_POS_TAB_2 (Number of positions for 1st/2nd indexing axis)
Standard value: 0 Maximum value: 60
Modify MD10910 $MN_INDEX_AX_POS_TAB_1 [n]
Modify MD10930 $MN_INDEX_AX_POS_TAB_2 [n]
(Positions of the 1st indexing axis) The absolute axis positions are entered. (The list length is defined via MD10900
$MN_INDEX_AX_LENGTH_POS_TAB_1).
Program
Clear alarm with NC START or RESET key and continue the program.
Continuation:
17501
[Channel %1: ] Block %2 indexing axis %3 with Hirth tool system is active
Parameters:
%1 = Channel number
%2 = Block number, label
%3 = Axis name
Definitions:
The 'Hirth tooth system' function is activated for the indexing axis. This axis can therefore approach only indexing posi-
tions, another travel movement of the axis is not possible.
Reaction:
Interpreter stop
NC Start disable in this channel.
Interface signals are set.
Alarm display.
NC Stop on alarm.
Remedy:
Please inform the authorized personnel/service department.
Correct part program.
Correct FC16 or FC18 call.
Deselect machine data MD30505 $MA_HIRTH_IS_ACTIVE.
Program
Clear alarm with the RESET key. Restart part program
Continuation:
282
Diagnostics Manual, 07/2010, 6FC5398-8BP40-0BA0
Alarms