Sms Alarm Messages; Analog Inputs Configuration - Digicom Pocket AL I/O User Manual

Digicom alarm system via sms user’s guide
Table of Contents

Advertisement

Pocket AL I/O

3.4.1. SMS Alarm Messages

The message sent by the device in case of alarm to the devices set during the configuration will contain the following
information:
• Pocket AL I/O ID (i.e. HOME)
• Contact number (i.e. 1)
• Contact ID (i.e. GasAlarm)
• Status
ON (alarm condition)
OFF (standard operating condition)
Examples
Contact 1 alarm
HOME
1)GasAlarm ON
Contact 1 alarm off
HOME
1)GasAlarm OFF

3.5. ANAlOG INPUTS CONfIGURATION

Pocket AL I/O can read the values of two analog inputs where it is possible to connect analog sensors that operate with 4-20mA
power.
To each single contact you can associate an input mnemonic name, 2 threshold values that can define 3 or 2 zones and the detection
interval. Pocket AL I/O will monitor the analog input as set by the user. The messsage of treshold excedeed (and consequently
of zone change) referred to the previous detection must be always sent after the first detected value exceeding the treshold, that
is in the new zone.
#
KEY
#
ID
NAME
VALUE
Key
13,14
ID
A..Z,a..z,
0..9
Level1
0..1000
Level2
0..1000
Detection timer 1..999sec
User n
+ 0..9
NOTES
1. If you want to add a number to an already set list, it will be necessery to insert all the numbers again.
2. Pocket AL I/O will continuously monitor the analog input with the timer set by the user: Detection
timer.
3. You can set a single level by setting the value in Level1 and defining Level2 at the maximum value:
1000
4. By setting the field user1="0" it will manage the input the status of which can be read with "test"
command, but no sms will be sent.
EXAMPLES
#13#Temperature#154#501#5#+393359988776#+393491122334#+393285554446#
#14#Waterlevel#258#409#1#+393359988776#+393491122334#+393285554446#
# Level1 # Level2
# Detection Timer #
DESCRIPTION
Key of analog inputs: 13 e 14
ID associated to the contact (20 characters maximum. "#" and space characters not
accepted in the ID field)
Lower level (0 = 4mA 1000 = 20mA)
Higher level (0 = 4mA 1000 = 20mA)
Detection interval
Phone numbers to which the alarm message must be sent (up to six phone numbers can be
inserted)
USER 1 #
USER n
#
Configuration