L1/L2: First and second digit, respectively, of first zone of crossed zone group 1
L3/L4: First and second digit, respectively, of second zone of crossed zone group 1
Example: Locations 1, 2 = 11; Locations 3, 4 = 23. This results in a cross between zones 11 and 23.
Q 53 CROSSED ZONES TIME
This option sets the time period (number of seconds) in which both zones in a cross zone group must be
faulted for an alarm to be sent. The timer begins when either of the zones in a cross zone group is
faulted. Enter the digits as follows:
N/U
N/U
L1
L2
L3
not used
Group 1 Group 2
L3/L4
Cross Zone Time
Entry
(secs.)
15
0
30
1
45
2
3
60
4
75
90
5
105
6
7
120

Programming Submode 3: WIRELESS TRANSMITTER PROGRAMMING

Press [✱] + [BYPASS] while in Installer Mode 1, then press [3] to enter Wireless
Programming submode.
QUESTIONS 01–24 WIRELESS ZONE CONFIGURATION/SERIAL NUMBER
These questions assign the number of zones used by each transmitter and store the transmitter serial
numbers. See Installer Submode 2, Question 50, for assigning the first wireless zone number. Use the
separate Programming Form to enter the actual values for each zone.
L1: Number of zones (loops) used on the transmitter (1–4).
L3: Enter the cross zone time for group 1.
L4: Enter the cross zone time for group 2.
L4
L3/L4
Cross Zone Time
Entry
8
9
A
B
C
D
E
F
L1
L2
L3
No. of zones enable RF –––––––––––Transmitter 7-digit serial number –––––––––––––––
Section 6. System Programming
(secs.)
135
150
165
180
195
210
225
240
L4
L5
L6
L7
L8
L9
6–51