Modem Configuration Program (DOS)
DIALING SETUP
Type (Pulse or Tone): Selects the type of dialing the modem uses
when calling-in to another modem. Tone dialing must be available
from the local phone system before this option can be selected.
Dialing Speed: This parameter is used to specify the duration of the
tones in Dual Tone Multi-Frequency (DTMF) dialing. The default is
95 milliseconds and has no effect on pulse dialing. Values below 70
milliseconds can be too fast for some telephone switching equipment.
Auto Answer After: This setting will determine on what ring the
Mercury Modem will answer an incoming call. Placing a "0" in this
field will cause the Modem to ignore incoming calls.
Number of Retries: When an alarm condition occurs, this number
specifies the maximum number of primary call-in retries the modem
will attempt, if the modem fails to communicate with the host on the
initial call-in. (Rev is the modem board revision code)
Primary Retry Period:
Secondary Retry Period:
Default Value: 3 Retries
No Rev = Approx. 22 min.
A1 Rev = Approx. 11 min.
A2 Rev = Approx. 5 min.
No Rev = Approx. 48 hrs.
A1 Rev = Approx. 24 hrs.
A2 Rev = Approx. 11 hrs.