Hitachi PC-ARF Technical Catalogue page 99

Table of Contents

Advertisement

4 Individual remote controls
PC-ARF

Thermistor Selection
This function changes the temperature thermistor from indoor unit thermistor to thermistor of remote control switch or an
average between both temperatures.
1 Press and hold " " (menu) and " " (return) simultaneously for at least
3 seconds during the normal mode (when unit is not operated). The
test run menu is displayed then.
2 Select "Thermistor Selection" from the test run menu and press "OK".
3 Change the temperature thermistor item by pressing "
"OK".
4 Select "Yes" and press "OK". The test run menu is displayed after the
setting is confirmed. If "No" is pressed, the screen returns to step 3.
5 Press " " (return) on the test run menu to return to the normal mode.

Indoor Unit Address Change
This function changes the address (refrigerant cycle number and indoor unit number) of indoor units. If this setting is done,
it takes priority over DIP Switch setting.
1 Press and hold " " (menu) and " " (return) simultaneously for at least
3 seconds during the normal mode (when unit is not operated). The test
run menu is displayed then.
2 Select "I.U. Address Change" from the test run menu pressing "
and "OK".
3 Select the indoor unit by pressing "
* Indoor units which are not supporting "I.U. Address Change" function
can not be selected.
83
TCGB0106 rev.0 - 12/2014
" and press
"
" and press "OK".
01-01
02-01
03-01
04-01
02-02
03-02
04-02
01-02
01-03
02-03
03-03
04-03
01-04
03-04
04-04
4