5 Centralised remote controls
PSC-A32MN
Main Unit Registration
•
Only one unit can be registered as the main unit of a group. Thus, duplicate registration of the main unit is not possi-
ble inside a group. If the unit registered as the main unit has to be changed for some reason, then cancel the current
register of main unit before registering the new main unit again.
•
When the indoor units with fan speed of 4 and 3 tap are mixed in same remote control group, register the indoor unit
with fan speed of 4 tap as the main unit. If the indoor unit with fan speed of 3 tap is registered as the main unit, fan
speed setting of 4 tap cannot be applied for this group.
•
When mixing indoor units with automatic swing louvre and indoor units with automatic swing louvre together in the
same remote control group, an indoor unit with auto-louvre shall be registered as the main unit of the group. If an
indoor unit without auto-louvre is registered as the main unit, then the auto-louvre setting cannot be applied for the
entire group.
•
When registering a group which has no transmission wiring, the indoor unit without a remote control switch cannot be
registered as the main unit.
Sub Unit Registration
•
A maximum of 15 sub units can be registered in the same remote group with the main unit (when applying the control
pattern of 2 blocks with 16 groups each).
•
Indoor units without a remote control switch cannot be registered as sub units.
•
In case of changing the registration of an indoor unit which is already registered as a sub unit, cancel the register set-
tings first, and then proceed to the new register.
Registration of a group (Main unit)
1 Select "Group Register" on the "Service Menu" screen.
(1)
N O T E
This function cannot be selected when the external input signal is input to the external input terminal 1 or 2.
2 Select "Main Unit Register" on the "Group Register".
(2)