7 Gateways for building management systems
HARC-BX E
b. XIF file variables
SVNT
Unit
Variable num-
number
number
ber
0
0
nviOnOff_0
1
0
nviMode_0
nviSet-
2
0
Point_0
nvi-
3
0
FanSpeed_0
4
0
nviProtect_0
5
0
nvoOnOff_0
nvoIn-
6
0
letTemp_0
7
1
nviOnOff_1
8
1
nviMode_1
nviSet-
9
1
Point_1
nvi-
10
1
FanSpeed_1
11
1
nviProtect_1
12
1
nvoOnOff_1
nvoIn-
13
1
letTemp_1
678
678
TCGB0106 rev.0 - 12/2014
LONMARK
Type
SNVT No.
SNVT_switch
95
SNVT_hvac_
108
mode
SNVT_
105
temp_p
SNVT_switch
95
SNVT_switch
95
SNVT_state
83
SNVT_
105
temp_p
SNVT_switch
95
SNVT_hvac_
108
mode
SNVT_
105
temp_p
SNVT_switch
95
SNVT_switch
95
SNVT_state
83
SNVT_
105
temp_p
Description
Byte 1: Value 0 (Fixed)
On/Off order
Byte 2: State 0 = STOP
1 byte:
1 = HVAC_HEAT (Heat-
ing)
3 = HVAC_COOL (Cool-
Operation mode
ing)
setting
5 = HVAC_PRE_COOL
(Dehumidification)
9 = HVAC_FAN_ONLY
(Ventilation)
2 Bytes: 1700 ~ 3000 = 17
Temperature setting
~ 30 ºC
Byte 1: Value 1: Low,
Fan speed setting
Byte 2: State 0 (Fixed)
Byte 1: Value 0 (Fixed)
Byte 2: State 0: RCS
Remote control order
enabled
32 bits:
ON/OFF state and
bit 0: 0 (STOP)/1 (RUN)
alarm notification
bit 1: 0 (Normal) /1
(Alarm)
Indoor temperature
2 Bytes: -6200 ~ 12700 =
reading
-62 ~ 127 ºC
Byte 1: Value 0 (Fixed)
On/Off order
Byte 2: State 0 = STOP
1 byte:
1 = HVAC_HEAT (Heat-
ing)
3 = HVAC_COOL (Cool-
Operation mode
ing)
setting
5 = HVAC_PRE_COOL
(Dehumidification)
9 = HVAC_FAN_ONLY
(Ventilation)
2 Bytes: 1700 ~ 3000 = 17
Temperature setting
~ 30 ºC
Byte 1: Value 1: Low,
Fan speed setting
Byte 2: State 0 (Fixed)
Byte 1: Value 0 (Fixed)
Byte 2: State 0: RCS
Remote control order
enabled
32 bits:
ON/OFF state and
bit 0: 0 (STOP)/1 (RUN)
alarm notification
bit 1: 0 (Normal) /1
(Alarm)
Indoor temperature
2 Bytes: -6200 ~ 12700 =
reading
-62 ~ 127 ºC
Condition
Note
State 1 = RUN
Allow an in-
terval of at
least 5 sec.
between 2
consecu-
tive orders
to any unit
on a H-Link
Value 2: Middle,
Value 3: High
enabled
State 1: RCS
disabled
Approxi-
mate up-
date time of
80 sec.
State 1 = RUN
Allow an in-
terval of at
least 5 sec.
between 2
consecu-
tive orders
to any unit
on a H-Link
Value 2: Middle,
Value 3: High
enabled
State 1: RCS
disabled
Approxi-
mate up-
date time of
80 sec.