Electrical Wiring - Hitachi PC-ARF Technical Catalogue

Table of Contents

Advertisement

8 Control support devices
PC-AMTB

8.5.3.2 Electrical wiring

1 Make sure that indoor unit is switched off, and then, open the electrical box.
2 Disconnect the Remote Control (RCS) cable from the electrical box terminals of the indoor unit and connect it into the
PC-AMTB screw terminals "RC-A,B".
3 Disconnect the H-LINK cable from the electrical box terminals of the indoor unit and connect it into the PC-AMTB
screw terminals "HLINK1-1,2".
4 Remove wire <4> from IU electrical box (from terminal box and "CN2" connector).
5 Connect wire <1> from PC-AMTB "HLINK 2" connector to IU PCB "CN2".
6 Disconnect EVI wire <3*> from IU PCB "CN11" and switch it to connector wire <3>. The other ending of wire <3>
must be switched to PC-AMTB "EV OUT".
7 Connect wire <2> between PC-AMTB "EV IN" and IU PCB "CN11".
8 Connect power wires <5> to PC-AMTB screw terminals "POWER SUPPLY".
INDOOR UNIT BEFORE PC-AMTB CONNECTION
INDOOR UNIT AFTER PC-AMTB CONNECTION
N O T E
PCB: Printed circuit board.
EVI: Indoor unit expansion valve.
Connectors in wires named after connectors in PC-AMTB and IU PCB.
740
TCGB0106 rev.0 - 12/2014
Indoor unit
PCB
Indoor unit electrical box
Indoor unit
PCB
Indoor unit electrical box
Indoor
unit
Indoor
unit

Advertisement

Table of Contents
loading

Table of Contents