Replacing The Closing And Opening Coil - GE GL 310 F3/4031 P/VR Operating Instructions Manual

High voltage circuit breaker
Table of Contents

Advertisement

8.2.2

Replacing the Closing and Opening Coil

CAUTION
REV6
/REV2
• Disconnect the wire connections from the coil (3).
1
Leaf spring
2
Yoke
3
Coil
4
Side plate
• Push aside the leaf spring (1) with your finger in the direction of
the arrow.
• Lift out the yoke (2) and place it on a clean surface.
Remove the coil being replaced and insert a new coil over the
side plates (4).
The wrong coil type can cause the mechanism to malfunction.
Make sure you have the correct coil type. Compare the part
number on the coils.
• Replace the yoke (2) and mount the leaf spring (1).
• Check the fit of the leaf spring (1): it must snap into place.
• Connect the coil (3).
OI 248 (EN)