C
OMMISSIONING
7.3

Filling the Breaker with Gas

CAUTION
7,5
7,0
6,5
6,0
5,5
5,0
4,5
4,0
3,5
-40
(1)=Nominal Density
(2)=Alarm Density
(3)=Lockout Density
(4)=Liquifaction Curve
48
All pressure specifications are given in terms of relative pressure
(p
).
e
• Connect the filling hose of the gas-filling device (gas cylinder with
pressure-reducing valve or gas handling cart) to the central
supply connection (type DILO DN8 coupling).
• Fill the circuit breaker gradually until rated pressure is reached.
Never set the pressure-reducing valve higher than the rated
breaker pressure.
• After a temperature equalization period of approximately 1 hour,
check the gas pressure again and correct it, if necessary.
• Check all gas piping seals for leaks using a leak detector.
• Screw on the protective cap for the central supply connection.
(4)
Liquid
Gaseous
-30
-20
-10
48,77 g/L
41,58 g/L
39,46 g/L
SF
pressure curve -30°C
6
(ND =0.64 MPa [p
e
1
Rated pressure curve
2
Alarm pressure curve
3
Lockout pressure curve
4
SF
liquefaction curve
6
OI 248 (EN)
0
10
20
t / °C
] / UW1=0.54 MPa [p
30
40
] / UW2=0.51MPa [p
e
-
-
-
-
REV6
(1)
(2)
(3)
50
])
e
/REV7