A5.3
Technical Data: Spring Operating Mechanism
Type
Motor for charging the closing spring
Rated voltage (preferred values)
- Direct voltage
- Alternating voltage
Allowable rated voltage deviation
Power consumption
Closing spring charging time
Shunt releases, closing and opening:
Rated supply voltage
(preferred values only with direct voltage)
Allowable rated supply voltage deviation
- Shunt closing release
- Shunt opening release
Power consumption of releases
- Shunt closing release
- Shunt opening release
Minimum pulse duration
Auxiliary circuits:
Rated continuous load current
Auxiliary contact tripping capability
- At 230 V alternating voltage
- At 220 V direct voltage in an inductive circuit with a
time constant of L/R = 20 ms
Anti-condensation heating unit:
Rated voltage (preferred values)
Power consumption
*) Specify when ordering
REV6
/REV3
V
V
W
s
V
W
W
ms
A
A
A
V
W
OI 248 (EN)
T
D
ECHNICAL
ESCRIPTION
60/110/125/220/250 *)
120/230 *)
85 to 110 % Vn
60/110/125/220/250 *)
85 to 110 % Vn
70 to 110 % Vn
120 or 230 *)
FK 3-1
≤ 1000
≤ 15
340
340
10
10
10
2
80
125