Piping Design "I" pipe - Single Channel (FLX-010):
Example:
1. Verification of project constraints and determination of aspirator speed
E
Exhaust pipe
F
First hole
L
Last hole
PL
Pipe length with low speed
with high aspirator speed
N
Number of holes
2. Calculate nominal step between holes and hole position deviation form nominal
S = L / ( Number of holes – 1 ) = 40 / 8 = 5 m (≥2.5m)
± 0.2*5m = ±1m
3. Determination of necessary Sensitivity Level and the hole diameters
Number of Holes
Aspirator speed, max 80m for H and 50m for L
Alarm Level Class C with/without filter
Alarm Level Class B with/without filter
Alarm Level Class A without filter only
53
I-pipe network, Class C with In-line filter
Exhaust pipe of 10m (E), First hole at 20m (F), Last hole at 40m from the first hole (L), 9 holes
Required
10m
20m
40m
10+20+40=70m
9
vity Le
hole d
2
2
H/L
Low
High
High
Rules
≤ 29 m
1 ÷ 30m-E
≤ 50 m
≤ 80 m
See Table
1
3
3
4
5
H/L
H/L
H/L
Low
Low
Medium
High
High
High
High
High
-
6
7
8
H/L
H/L
H/L
Medium
Medium
Medium
High
High
High
-
-
-
FAAST FLEX
1
9
H/L
Medium
2
High
High
-