FAAST FLEX Product Guide
Table 2-2: FAAST FLEX Detector Specifications (continued...)
Specification
Flow Fault
IP Rating
Mechanical
Exterior Dimensions
Wiring
Pipe Network Layout
Maximum Number of
Holes
Pipe Spec
(EN54-20 Compliance)
Outside Pipe Diameter
Shipping Weight
7
± 20% of the reference flow (according to EN54-20)
IP40
204 mm x 280 mm x 80.5 mm
0.5 mm² to 2.5 mm² maximum
Single Channel Model
Linear pipe length: 1 X 105m (344 ft)
l
Branched pipe length: 2 X 105m (344 ft) or 4 X 68m (223 ft)
l
Dual Channel Model
Linear pipe length: 2 X 105m (344 ft)
l
Branched pipe length: 4 X 105m (344 ft) or 8 X 49m (161 ft)
l
Note:
Results can be achieved using CAD.
Refer to section "9 Piping Design Guidelines" for more information.
EN 61386 (Crush 1, Impact 1, Temp 31)
27 mm (nom) or 25 mm (nom) with plug/adapter
1.7 kg (including sensors)
Value
FAAST FLEX