Honeywell FCI 1151 Installation

System sensor low profile, ionization plug-in smoke detector

Advertisement

Quick Links

DESCRIPTION
The System Sensor 1151 low profile ionization type smoke
detectors are specifically designed to meet the performance
requirements of fire detection/alarm systems. The 1151 ion-
ization detector uses a state-of-the-art, dual unipolar sensing
chamber. The detector is designed to provide open area de-
tection and, when installed in a two-wire base, is compatible
with FCI fire alarm control panels. The detector's operation
and sensitivity can be tested in place.
The 1151 detector is of plug-in construction and plugs into
the same base as the System Sensor 2151photoelectronic
smoke detector, making both models interchangeable. Bases
are available for two-wire, four-wire, 120 VAC four-wire op-
eration and also with an audible sounder.
Two visible LEDs on each detector flash every ten seconds
indicating that power is being applied to the detector. The
LEDs light steadily when the detector is in alarm. A remote
LED annunciator is available as an optional accessory.
The 1151 detector is Listed for use inside ducts up to a ve-
locity of 500 FPM.
Functional testing is performed by placing a test magnet
against the cover. The LED on the detector should light
within 30 seconds.
Field metering of detector sensitivity may be performed
with the aid of a voltmeter and Test Kit, MOD 400R.
APPROVALS
Sensitivity
Operating voltage
Standby current
Operating temperature
Relative humidity
Air velocity
Construction
Diameter
Height
Weight
Specifications are provided for information only, are not intended to be used for installation purposes, and are believed to be accurate. However, no responsibility is assumed by Fire Control
Instruments, Inc. for their use. Specifications subject to change without notice.
16 Southwest Park, Westwood, MA 02090 USA TEL: (781) 471-3000 FAX: (781) 471-3099
LOW PROFILE, IONIZATION
PLUG-IN SMOKE DETECTOR
·
Unique Dual Unipolar Sensor
Provides Exceptional Stability
·
Low Profile Construction
·
Easy plug-in of the Head to Base
·
Tamper-resistant Feature
·
Test Switch
·
360
·
Compatible with FCI Control Panels
·
Audible Sounder Base (Optional)
·
Field Metering of Detector Sensitivity
·
Removable Insect Screen and Cover
for Field Cleaning
·
Insect-resistant Screening
(.020"/.508 mm openings)
SPECIFICATIONS
1.9 %/ft. (nominal)
15 - 32 VDC peak
200 uA max. avg.
o
32 to 120
F (0 to 49
10 to 93 % (non-condensing)
500 feet per minute maximum
Off-white flame retardant plastic
4 inches (10.2 cm)
1.7 inches (4.2 cm)
3.6 oz. (104 g)
An ISO 9001 Certified Company
1151
SYSTEM SENSOR
FEATURES
o
View Angle Of Alarm LEDs
o
C)
© 2003 All Rights Reserved
9020-0582/Ver. 1.1

Advertisement

loading

Summary of Contents for Honeywell FCI 1151

  • Page 1 1151 SYSTEM SENSOR LOW PROFILE, IONIZATION PLUG-IN SMOKE DETECTOR DESCRIPTION The System Sensor 1151 low profile ionization type smoke detectors are specifically designed to meet the performance requirements of fire detection/alarm systems. The 1151 ion- ization detector uses a state-of-the-art, dual unipolar sensing chamber.
  • Page 2 MOUNTING · On a 4-inch square box with or without plaster ring. Minimum depth 1.5 inches. · On a 3.5-inch octagonal box. Minimum depth 1.5 inches. INSTALLATION Place the detector into the detector base. Turn the de- tector clockwise until the detector locks into place. To use the tamper-proof feature, break the smaller tab on the scribed line in the tamper proof tab located on the detector mounting bracket.