Piping Considerations - Honeywell Xtralis FAAST FLEX FLX-010 Product Manual

Table of Contents

Advertisement

FAAST FLEX
3.6

Piping Considerations

1. Inlet ports that are not used should remain sealed.
Caution:
DO NOT glue piping into the inlet and exhaust ports. Pipes that are glued in will be deemed out
of warranty, since they cannot be tested.
2. To avoid contamination by dust, debris, insects, or spiders, It is recommended that inlet and exhaust
ports remain plugged before use. Seal up inlet and exhaust ports if the device is turned off during
maintenance periods.
3. Whenever the FAAST FLEX is installed outside the risk area, it is recommended that the exhaust air
from the device be returned to the risk area. This will reduce flow faults caused by pressure differences
(see Figure 3-7).
4. DO NOT USE GLUE OR ADHESIVE. The FAAST FLEX ports are designed to provide a complete seal
without the use of any adhesives, glues, or other substances.
5. The FAAST FLEX is designed to accommodate either 27mm or 25mm pipe. If 25mm piping is used, an
adapter is required. On the inlets, the pipe plugs can be used as an adapter by removing the center of the
plug to open it up (see Figure 3-8). On outlet piping, the screen can be used as an adapter with 25mm
piping (see Figure 3-9).
www.xtralis.com
Figure 3-7: Piping Considerations
FAAST FLEX Product Guide