6.5.2
EEPROM Factory Reset
To perform a reset to the default EEPROM configuration, perform the following steps.
Action
Open cover and allow
device to enter SERVICE
Mode (60 second wait).
Set all DIP Switches to ON
position.
Long press the RESET
button.
Enter the passcode.
If the LEDs show red, repeat the process by long pressing the RESET button again. This can happen in an
undervoltage situation.
Note:
If the reset procedure fails a second time the device is corrupted and must be replaced with a new
unit.
44
Button
LED Display
1
3
2
4
Long
Press
1
3
2
4
Description
LED 5 will fast blink red when
the device enters SERVICE
5
Mode.
6
LED 5 will go out and LEDs 1,
2, 3, and 4 will flash yellow,
and the buzzer will sound to
indicate that the reset
procedure has been started.
Once the passcode is entered,
the device will be reset to the
EEPROM factory settings.
Note:
The passcode is
NOT changed.
All LEDs will show green for 2
seconds to indicate the reset
5
was successful.