FAAST FLEX Product Guide
6.2

NORMAL Mode

This is normal working mode. The device monitors the power supply voltage, aspirator speed, smoke levels,
air flows, cover status, and signals and logs faults, actions, alarms.
6.3

WAIT Mode

The WAIT mode is a sub-mode of the NORMAL mode. There are two ways to enter into the WAIT mode:
1. If the cover is open the device enters WAIT mode after power-on and initialization.
2. If the cover is opened while the device is in NORMAL mode.
On entering WAIT Mode the POWER LED blinks yellow (slow blink). At this point the device is waiting for a
button press.
After 60 seconds of no activity in WAIT mode the device will automatically go into the SERVICE mode. Every
time an action (button or BLT) is performed in WAIT mode the timeout timer restarts. If a non-protected action
(no passcode required) is requested, the command is executed and then the device comes back to WAIT
mode. If a protected action (passcode required) is requested, user is prompted to enter the passcode. If the
passcode is correct the device will perform the requested action.
WAIT Mode Actions
Note:
For a long press of a button, press and hold it for 5 seconds.
Action
Toggle button beeps ON/OFF
Initiate NORMALIZE procedure
(Passcode Authentication
Required - if not authenticated,
you must enter the passcode to
start procedure.)
Copy LOGREPOR.TXT to USB
drive
Enter CHANGE CONFIGURATION
MODE
(Passcode Authentication
Required)
Reset active Alarms or Faults
(Passcode Authentication
Required)
Toggles DISABLE Mode ON/OFF
(This option is NOT AVAILABLE
if GPI is disabled in extended
mode)
20
Table 6-1: WAIT Mode Actions
Button
LED Display
Short
Press
1
3
2
4
Long
Press
Short
Press
Long
1
3
Press
2
4
Short
Press
Long
Press
1
3
2
4
FAAST FLEX
Description
LED 6 will show green ON
5
for 3 seconds as feedback.
Default beeps ON.
6
LEDs 1 through 4 will show
yellow to indicate that the
NORMALIZE procedure
has started. See section
6.3.4 Normalize.
USB drive must be
inserted. See section 6.3.6
Event Logs for more
information.
LEDs 1 through 4 will show
yellow to indicate change
5
configuration procedure has
started. See section 6.3.3
Changing Configuration
6
Mode.
Resets the latched alarm
and faults status.
LEDs 1 through 4 will show
5
yellow to indicate disable
mode has turned ON/OFF.
6
www.xtralis.com