Final Door Install (continued)
28.2 Place the Operator into hoist mode by pulling the hoist release cord.
28.3 Turn Reset Test Switch to TEST position. The notification appliance will sound indicating a door closure is about to occur, and after a 10 second factory
set alarm delay (or optional longer delay) the Fire Door Operator will mechanically release door and door will close.
28.4 Release the hoist cord.
28.5 Turn Reset Test Switch to RESET position and then back to NORMAL.
28.6 Press the open button to raise the door. (Door may auto open).
Keep the door opening clear of all personnel.
28.7 Turn off power to the Fire Door Operator.
28.8 "External Power Loss, " "Battery Not Charging, " and "Control Board Error" LEDs on FDM will be generated in approximately 10 seconds. This is a normal
condition.
28.9 Turn the Reset Test Switch to the TEST position. The notification appliance will sound indicating door closure is about to occur and after a 10 second
factory set alarm delay (or longer optional delay) the Fire Door Operator will mechanically release the door.
28.10 Turn the Reset Test Switch to the RESET position and then back to NORMAL. This test verifies a mechanical release in absence of power to the Fire
Door Operator.
28.11 Restore power to the Fire Door Operator and raise the door to the fully open position.
28.12 Turn the Reset Test Switch to RESET and back to NORMAL to clear trouble indicator on the Reset Test Switch.
29. AUTOMATIC DOOR CLOSURE TEST
29.1 Open door to full open position.
29.2 Make sure that the "FD OBSTCT CYL" are set to "3" and the "FD STP ON OB" is set to OFF.
Keep the door opening clear of all personnel.
29.3 Place a chair or other suitable obstruction in the normal path of the door. Stand clear of door opening.
29.4 Turn the key-switch to TEST and leave it there. The notification appliance will turn on indicating that a door closure is about to occur. After the factory
set 10 second (or optional longer) delay, the Fire Door Operator will initiate a closure.
• Upon contact with the obstruction, the safety edge will reverse the motor and raise the door to the up limit. The Fire Door Operator will make three
attempts to close the door, after the third reversal it will release the door through the electrical clutch.
• STAND CLEAR OF ANY PATH THE OBSTRUCTION MIGHT TAKE AFTER BEING CONTACTED BY THE DROPPED DOOR.
• The door will drop onto the obstruction and will fully close once the obstruction is removed. The notification appliance will continue to sound until the
alarm condition is cleared. (Unless QUIET @ DN is set to ON).
29.5 Reset the Fire Door Operator by turning the key-switch to the RESET position and then back to NORMAL. (Door may auto open)..
830872-0001
REV 12/07/2022