76 Electrical installation – IEC

Default fieldbus connection diagram

The connection diagrams are applicable to the base unit with an optional fieldbus adapter
module. ABB standard macro (parameter 96.04) is used with its default parameter
settings.
Connection
Auxiliary voltage output and digital inputs
+24 V
+24 V
DGND
DGND
DCOM
DCOM
DI1
DI1
DI2
DI2
Relay outputs
+24 V
DGND
DCOM
RO1C
RO1A
RO1B
Safe torque off
SGND
IN1
IN2
OUT1
Fieldbus connection
See the applicable
fieldbus adapter manu-
al.
1) Terminal size: 0.14 ... 1.5 mm 2 (26 ... 16 AWG) Tightening torque: 0.5 ... 0.6 N·m (4.4 ... 5.3 lbf·in)
1)
Description
Terminal
10
+24V
Aux. voltage output +24 V DC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1)
14
DI2
Forward (0) / Reverse (1)
10
+24V
Aux. voltage output +24 V DC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
19
RO1C
Common
20
RO1A
Norm. closed
21
RO1B
Norm. open
34
SGND
Safe torque off. Factory connection. Both circuits
must be closed for the drive to start.
35
IN1
36
IN2
37
OUT1
DSUB9
+K457 FCAN-01 CANopen
DSUB9
+K454 FPBA-01 Profibus DP
RJ45×2
+K469 FECA-01 EtherCAT
RJ45×2
+K475 FENA-21 Ethernet/IP, Profinet, Modbus
TCP
RJ45×2
+K470 FEPL-02 Ethernet Powerlink
Terminal
+K451 FDNA-01 DeviceNet
block
8P8C×2
+K462 FCNA-01 ControlNet
RJ45×2
+K490 FEIP-21 Two-port Modbus/IP adapter
RJ45×2
+K491 FMBT-21 Two-port Modbus/TCP adapter
RJ45×2
+K492 FPNO-21 Two-port Profinet IO adapter
Ready run
250 V AC / 30 V DC, 2 A
2)
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×