Connection Procedure - ABB ACS480-04-09A8-1 Hardware Manual

Table of Contents

Advertisement

72 Electrical installation – IEC

Connection procedure

WARNING!
Obey the safety instructions of the drive. If you ignore them, injury or death,
or damage to the equipment can occur. If you are not a qualified electrical
professional, do not do installation or maintenance work.
Refer to
Terminal data for the power cables (page 156)
1. Do the steps in section
work.
2. Remove the screw on the drive front cover and lift the front cover up.
3. Attach the residual voltage warning sticker in the local language to the drive.
4. Strip the motor cable.
5. Ground the motor cable shield under the grounding clamp for 360-degree grounding.
6. Twist the motor cable shield into a bundle, mark it with yellow-green insulation tape,
install a cable lug, and connect it to the grounding terminal.
Electrical safety precautions (page 18)
for the tightening torques.
before you start the

Advertisement

Table of Contents
loading

Table of Contents