Not Allowed Power Cable Types - ABB ACS480-04-09A8-1 Hardware Manual

Table of Contents

Advertisement

50 Guidelines for planning the electrical installation
Cable type
PE
A single-core cable system:
three phase conductors and
PE conductor on cable tray
L1
L2
L2
L3
L3
L1
L1
Preferable cable arrangement
to avoid voltage or current un-
balance between the phases
1) Armor may act as an EMC shield, as long as it provides the same performance as a concentric EMC shield
of a shielded cable. To be effective at high frequencies, the shield conductivity must be at least 1/10 of the
phase conductor conductivity. The effectiveness of the shield can be evaluated based on the shield inductance,
which must be low and only slightly dependent on frequency. The requirements are easily met with a copper
or aluminum shield/armor. The cross-section of a steel shield must be ample and the shield helix must have
a low gradient. A galvanized steel shield has a better high-frequency conductivity than a non-galvanized steel
shield.

Not allowed power cable types

Cable type
Symmetrical shielded cable
with individual shields for each
phase conductor
Use as input power cabling
Yes
WARNING!
If you use unshielded
single-core cables in an
IT network, make sure
L3
that the non-conductive
L2
outer sheath (jacket) of
the cables have good
contact with a properly
grounded conductive sur-
face. For example, install
the cables on a properly
grounded cable tray. Oth-
erwise voltage may be-
come present on the non-
conductive outer sheath
of the cables, and there
is even a risk of an elec-
tric shock.
Use as input power cabling
No
PE
Use as motor cabling
No
Use as motor cabling
No

Advertisement

Table of Contents
loading

Table of Contents