Terminal Data For The Power Cables - ABB ACS480-04-09A8-1 Hardware Manual

Table of Contents

Advertisement

156 Technical data

Terminal data for the power cables

IEC type
L1, L2, L3, T1/U, T2/V, T3/W, R-, R+/
ACS480-
04-...
Minimum
(solid/stran-
ded)
mm 2
1-phase U N = 230 V
02A4-1
0.5/0.5
03A7-1
0.5/0.5
04A8-1
0.5/0.5
06A9-1
0.5/0.5
07A8-1
0.5/0.5
09A8-1
0.5/0.5
12A2-1
0.5/0.5
3-phase U N = 230 V
02A4-2
0.5/0.5
03A7-2
0.5/0.5
04A8-2
0.5/0.5
06A9-2
0.5/0.5
07A8-2
0.5/0.5
09A8-2
0.5/0.5
12A2-2
0.5/0.5
17A5-2
0.5/0.5
25A0-2
0.5/0.5
032A-2
0.5/0.5
048A-2
0.5/0.5
055A-2
0.5/0.5
3-phase U N = 400 V
02A7-4
0.5/0.5
03A4-4
0.5/0.5
04A1-4
0.5/0.5
05A7-4
0.5/0.5
07A3-4
0.5/0.5
09A5-4
0.5/0.5
12A7-4
0.5/0.5
018A-4
0.5/0.5
026A-4
0.5/0.5
033A-4
0.5/0.5
039A-4
0.5/0.5
UDC+
Maximum
Tightening
(solid/stran-
torque
ded)
mm 2
N·m
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
10/6
1.2...1.5
10/6
1.2...1.5
25/16
2.5...3.7
25/16
2.5...3.7
25/16
2.5...3.7
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
4/2.5
0.5...0.6
10/6
1.2...1.5
10/6
1.2...1.5
25/16
2.5...3.7
25/16
2.5...3.7
PE
Minimum
Maximum
(solid/stran-
(solid/stran-
ded)
ded)
mm 2
mm 2
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
10/6
25/16
10/6
25/16
10/6
25/16
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
4/2.5
6/4
10/6
25/16
10/6
25/16
Tightening
torque
N·m
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
2.9
2.9
2.9
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
1.2
2.9
2.9

Advertisement

Table of Contents
loading

Table of Contents