102 Electrical installation – North America
Connection
Auxiliary voltage input/output
+24 V
DGND
DCOM
1) Terminal size: 0.14 ... 1.5 mm 2 (26 ... 16 AWG) Tightening torque: 0.5 ... 0.6 N·m (4.4 ... 5.3 lbf·in)
2) × = base unit, empty = RIIO-01 module
3) The sum output current from 24 V terminals of base unit and RIIO-01 module must not exceed 250 mA.
4) Drive output frequency:
DI3
DI4
0
1
0
1
5) See parameters 28.72, 28.73, 28.74 and 28.75.

Default fieldbus connection diagram

The connection diagrams are applicable to the base unit with an optional fieldbus adapter
module. ABB standard macro (parameter 96.04) is used with its default parameter
settings.
Connection
Auxiliary voltage output and digital inputs
+24 V
+24 V
DGND
DGND
DCOM
DCOM
DI1
DI1
DI2
DI2
Relay outputs
+24 V
DGND
DCOM
RO1C
RO1A
RO1B
1)
Description
Terminal
42
+24V
Aux. voltage output +24 V DC, max. 250 mA
43
DGND
Aux. voltage output common
44
DCOM
Digital input common for all
Operation/Parameter
0
Set output frequency through AI1
0
28.26 Constant frequency 1
1
28.27 Constant frequency 2
1
28.28 Constant frequency 3
1)
Description
Terminal
10
+24V
Aux. voltage output +24 V DC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
13
DI1
Stop (0) / Start (1)
14
DI2
Forward (0) / Reverse (1)
10
+24V
Aux. voltage output +24 V DC, max. 250 mA
11
DGND
Aux. voltage output common
12
DCOM
Digital input common for all
19
RO1C
Common
20
RO1A
Norm. closed
21
RO1B
Norm. open
Ready run
250 V AC / 30 V DC, 2 A
2)
3)
2)
×
×
×
×
×
×
×
×
×
×
×