Display Setup
The S7800A1167 Keyboard Display Module (KDM) requires a
password to enter the Display Setup Menu.
The Display Setup Menu offers the following functions:
— Clone—Allows the current display setup to be copied
entirely to another display (Series 3 or greater)—page
25.
— MB Address---Enables the ModBus Feature and Loca-
tion. The 7800 SERIES device is located on the Mod-
Bus highway. It also provides a means of system
verification that ModBus is active and that this module
is being addressed—page 26.
— MB Baud---Sets the data Transmit/Receive rate. The
S7800 is operating on ModBus—page 27.
— Clear All—Resets the Display settings back to the
factory settings—page 27.
— Password—Change current default password of 000 to
a unique one the customer has selected—page 27.
— CEA Edit—Configurable Expanded Annunciator allows
editing of messages 44 to 64 with a text message up to
12 characters in length. See Table 9 for available char-
acters—page 37.
— CEA Assign—Allows assigning a message to a given
Expanded Annunciator terminal, so when it shows up
on the display the description will match the specific
system interlocks connected to that Expanded
Annunciator terminal. See Table 8 for current message
text list (messages 4 through 22), messages 23
through 44 contain other commonly used messages
that could be chosen or assigned. Messages 45
through 64 are editable text strings edited through CEA
Edit—page 28.
— CS On/Off—Allows the Customer Service message to
be displayed or the lockout message to be displayed—
page 31.
— CS Test—Allows the Customer Service message to be
viewed for accuracy. This will display just once—page
31.
— CS Edit—Allows for personalizing a Customer Service
message. Three screens of messages are available.
Each screen has two lines with 20 characters available.
See Table 9 for available character text—page 37.
Display Setup—CLONE
CLONE allows copying your entire Custom Display to
additional displays, Series 4 or higher.
Before you begin, you will want to build a cloning jig.
7800 SERIES S7800A1167 KEYBOARD DISPLAY MODULE
MASTER
1
2
3
4
5
203541 FIVE-WIRE
CONNECTOR
Fig. 20. Cloning jig.
To access the CLONE menu:
Press the left three buttons of the KDM for one second, then
release.
DISPLAY Setup will appear. If you have a personal
password, enter it to enter Setup.
Edit:
-
Fig. 21. Display Setup screen.
Press ENTER by pressing the two ENTER buttons at the
same time.
Fig. 22. Select/Exit screen.
Choose Select.
Fig. 23. Display Setup/CLONE screen.
Press ENTER by pressing the two ENTER buttons at the same
time. The Select/Exit Screen (see Fig. 22) will appear. Choose
Select.
25
SLAVE
1
2
3
4
5
203541 FIVE-WIRE
CONNECTOR
_
+
13 VDC POWER
SUPPLY (203968
FOR EXAMPLE)
+
M22890
M22880
65-0311—02