7800 SERIES S7800A1167 KEYBOARD DISPLAY MODULE
Address
Register
(hex)
(dec)
0055
40086
BC Flame Amplifier type
0056
40087
BC Purge Time
0057-
40088-
BC Diagnostics
0065
40102
0066
40103
Post-Purge time
0067
40104
Valve Proving Mode
0068
40105
Valve Proving option
0069
40106
Valve Proving time
0066-
40103-
Unused
007E
40127
007F
40128
BC Remote Command
01B7-
40440-
Unused
01B8
40441
01BA
40443
Device Data Ready
01BB
40444
S7800 Device Compatibility
with Current Software
Revision
S7800 Software Revision
Compatibility with Legacy
Software Revisions.
NOTE: "Device Data Ready" and "S7800 Compatibility" bits can be used to quickly check device availability and compatibility
then read/write registers of only these devices.
Response Message Format for Function
Code 17.
This format is device specific and is only available for the 7800
SERIES burner control. See Table 14.
65-0311—02
Table 17. ModBus™ Register Assignments. (Continued)
Read/
Parameter Name
Write Format
R
R
R
R
R
R
R
R/W
U16
0 = Standard
1 = Unknown
2 = Amplicheck or missing amplifier
3 = Shutter
U16
Seconds
U16
String codes indicating terminal/jumper state. See Table 20. There
are up to 15 codes. Not all are used for some burner controls.
U16
Seconds
U16
0 = Valve Proving is not enabled
1 = Enabled before Run
2 = Enabled after Run
3 = Enabled before and after Run
4 = Enabled split half before and half after Run
U16
1 = Uncommissioned
2 = Commissioned
U16
Seconds
U16
Only one bit in the LSByte must be set, with the exception of bit 15:
Bit 0 =Revert to autonomous operation.
Bit 1 = Don't fire, remain off.
Bit 2 = Go to Hi Fire during Run.
Bit 3 = Go to Lo Fire during Run.
Bit 4 = Remote reset.
Bits 5-7 must be 0.
Bits 8-14 are ignored.
Bit 15: Copied to the control status register. The remote
control status register can be used to verify operation of the
command.
Bits 1-3 must be refreshed at least every 120 seconds, but
not more than once a second, for the burner control to
remain in the commanded state.
U32
U16
Device data was properly received by S7800.
Bit(s)
0
3
4-15
U16
Device is compatible with the S7810M version
Bit
0
3
4-7
Used for indication of S7800 revision compatibility.
Bit(s)
8
9-15
40
Notes
a
Device
RM78XX
EC78XX
Unused
Device
RM78XX
EC78XX
Unused
Compatible with:
Series 2
Future