Honeywell 04230-A-1001 Technical Handbook page 97

Searchline excel infrared gas detectors
Table of Contents

Advertisement

MAN0530 Issue 15 - 07/17
2104M0506
APPENDIX A - HANDHELD INTERROGATOR
Notes:
1.
The time and date will not be updated unless both are entered and accepted without
error.
2.
The year 2000 is displayed as 00.
Cal Sensor
This menu option zeros the system.
Notes:
1.
The 4-20 output is inhibited during this procedure. See the earlier description.
2.
There must be no gas in the system beam path whilst this procedure is carried out.
The following message is displayed:
The following message is displayed while the calibration operation is being performed:
If the calibration is successful, the following message is displayed for a period of three
seconds:
Force mA
This option allows the system's analogue output signal to be adjusted to a fixed level, e.g. when
setting up a system controller. The following message is displayed:
mmmmm
where:
This is adjusted using the
After adjustment the output is forced to the set level and the following message is displayed:
mmmmm
where:
Ensure Zero Gas
Press Enter
Processing Data
Please Wait...
Zero Calibrated
O/P current mA
Current to output.
and
keys over the range 1mA to 21mA in steps of 0.1mA.
Fixed:
Press Enter
Analogue output current previously set.
mmmmm
mmmmm mA