Table 4–1 IOEC module configuration - analog inputs
No. of I/O
Resolution
Signal interface
Signal level
Input resistance
Common mode voltage Maximum: 48 V
Isolation level
Table 4–2 IOEC module configuration - analog outputs
No. of I/O
Signal range
Resolution
Isolation level
Table 4–3 IOEC module configuration - digital inputs
No. of I/O
Signal level
Logical threshold
Input current
Isolation level
PRODUCT
ACS1000i
4
10 bit
Floating, galvanically isolated
0 to 20 mA, 4 to 20 mA, 0 - 10 V, 2 to 10 V
Individually scalable by parameter
R
= 105
for current input
in
R
= 250 k
for voltage input
in
350 V (AC)
2
0 to 20 mA (load impedance: maximum 250
12 bit
350 V (AC)
14
22 to 120 V (DC) *
*for the 80 to 120V range, an IOEC adapter board is required
22 to 250 V (AC)
≙ "0", > 16 V (AC or DC) ≙ "1"
< 13 V (AC or DC)
13 mA steady state (14 mA maximum inrush) at 24 V (DC)
11.5 mA steady state (80 mA maximum inrush) at 120 V (DC)
10.5 mA steady state (92 mA maximum inrush) at 230 V (AC)
1350 V (AC)