Honeywell MAXPRO MPIP2000U Series Installation And Setup Manual page 73

Integrated security systems
Table of Contents

Advertisement

Honeywell MAXPRO Intrusion MPIP2000U/3000U Series
# Item
E ENTRY
Reader
(Reader 1)
F
Triggers
G Door status
monitor
H Door
Strike/Lock
(relay)
I
Transient protection for magnetic lock or door strike
J
Auxiliary power supply for door strike/lock relay.
K Jumper
800-23044 Rev.  A draft_11
Terminal or
Connect to
connector
+12V
Entry reader power input [+].
Entry reader input [–] for power and
tamper
D0
Entry reader data 0
D1
Entry reader data 1
T
Entry reader tamper.
LED R
Entry reader red LED. If used: exit reader
red LED.
LED Y
Entry reader yellow LED. If used: exit
reader yellow LED.
LED G
Entry reader green LED. If used: exit
reader green LED.
BUZZ
Entry reader buzzer. If used: exit reader
buzzer.
Reader LEDs and buzzer [–] terminal.
Door status monitor [–] terminal.
DSM
Door status monitor.
Default supervision: EOLR (2K). For details and more
options, see Wiring Inputs (Zones) on page 39. Terminate
using resistors if not used.
Can be used as an entry/exit zone for burglary
protection.
NC
Normal Closed terminal
C
Common terminal
NO
Normal Open terminal
For door lock only: magnetic lock OR door strike.
Jumper for door strike/lock relay: 12 VDC feed for the
relay NC/NO contact if jumper is positioned over pins 1
and 2. For details, see further below.
Installation and Setup Guide
73