Honeywell MAXPRO MPIP2000U Series Installation And Setup Manual page 44

Integrated security systems
Table of Contents

Advertisement

Installation and Setup Guide
Compatible 2-Wire Smoke Detectors
Detector type
Photoelectric smoke detector
Photoelectric smoke detector with thermal sensor
Photoelectric smoke detector with thermal sensor
and sounder
Photoelectric smoke detector with thermal sensor
and Form C relay
Photoelectric smoke detector with heat sensor
Heat detector
Note
Not all listed devices may be available in all regions. Contact your local
Honeywell Intrusion Sales Representative for availability in your
region.
Wiring Fire Zones
Caution!
You must use EOL resistors on fire zones when configured for use
with smoke sensors, and across the loop wires of each zone at the
last detector.
Do not use the – (negative) terminals on zones 9 and 10 for anything
else than the zone wiring itself. They are not connected to the
common ground.
Connect 2-wire smoke detectors across zone 9 or 10 terminals (+ and –) as
shown below. Observe proper polarity when connecting the detectors.
You must connect the EOL resistor across the loop wires at the last detector.
A
A = End of line resistor; B = 2-wire smoke detector; C = terminals of zone 9/10.
44
Honeywell MAXPRO Intrusion MPIP2000U/3000U Series
B
Device model no.
System Sensor 2W-B
System Sensor 2WT-B
System Sensor 2WTA-B
System Sensor 2WTR-B
System Sensor 2151T
System Sensor 5151
C
800-23044 Rev.  A draft_11