Honeywell AlarmNet GSMBR Installation And Setup Manual page 25

Communications module
Table of Contents

Advertisement

PROMPTS
46
Subnet Mask:
255.255.255.255_
47
Gateway IP Addr:
255.255.255.255_
48
DNS Serv IP Addr:
255.255.255.255_
49
Enable Pwr Save
(Y)_
50
IP Connection
(Present)_
51
Review? Y/N
Programming for ECP Mode
ENTRY
OPTIONS
12 digit:
xxx.xxx.xxx.xxx
12 digit:
xxx.xxx.xxx.xxx
[0.0.0.0.] = not
used
12 digit:
xxx.xxx.xxx.xxx
[0.0.0.0.] = not
used
[Y], [N]
Present
Auto Detect
[Y] = review
[N] = exit
DESCRIPTION
Enter the 32-bit address mask used to indicate the
portion (bits) of the IP address that is being used for
the subnet address. Each part of the address must be
separated by spaces (displayed as periods in Review
mode).
Enter the 4-part address assigned to the Gateway.
Each part of the address must be separated by spaces
(displayed as periods in Review mode).
Enter the 4-part IP address assigned to the DNS
(Domain Name System) server. Each part of the
address must be separated by spaces (displayed as
periods in Review mode).
For 24 hour Battery Backup requirement, this feature
must be enabled, or the unit must be powered by an
Uninterruptible Power Supply. If connectivity
problems occur with certain routers or switches disable
this option.
Press the [space] key to toggle between the options.
Press [ENTER] to select the configuration.
If "Present" is chosen, it is assumed that an IP is
connected to the device. If it is not detected, a Primary
Comm Path Failure message will be delivered after the
programmed fault time expires.
If "Auto Detect" is chosen, the device will always try to
use IP to communicate but it will not generate a
Primary Comm Path Failure unless it previously
detected the presence of IP. As soon as the presence of
IP is detected, a Primary Comm Path Restore message
is generated and the value of IP Connectivity
programming parameter is changed from "Auto Detect"
to "Detected".
From this point on, the software expects connectivity.
The auto detect logic will resume only when the
parameter is changed back to "Auto Detect".
Reviewing Programming Mode Entries
To review the programming options (to ensure that the
correct entries have been made), press [Y]. The
programming prompts are displayed again. Use the
up/down arrow keys to scroll through the program
fields without changing any of the values. If a value
requires change, simply type in the correct value. When
the last field is displayed, the "REVIEW?" prompt
again appears.
To exit the programming mode, press [N] in
response to the "REVIEW?" prompt, and refer to
Exiting Programming Mode at the end of this section.
Section 3: Programming
3-9

Advertisement

Table of Contents
loading

This manual is also suitable for:

Alarmnet igsmbr

Table of Contents