Figure 3-8: Installation of reflecting plate

Installations with Agitation

If there are agitators in the tank, the instrument should be installed as far away from these as
possible. Once the installation is completed, the ""virtual echo learning" should be carried out
while the agitators are running. This will eliminate the influence of false echo generated by
mixing blades. If foam or wave is generated due to agitation, then the customer should consider
a guided wave radar sensor such as the Honeywell SLG-700 series.
Go to
https://www.honeywellprocess.com/en-US/explore/products/instrumentation/process-
level-sensors/Pages/smartline-guided-wave-level-transmitter.aspx

Figure 3-9: Agitation

Page 12
SLN 700 SmartLine NCR Level Transmitter User's Manual
Revision 1