4.3 Reset to
Factory
Settings
4.4 Distance
Adjust
4.5 Echo
Threshold
Revision 1
Reset function is used to revert the instrument parameters back to the
initial factory settings. When displaying the current output (menu
number 4.2), press
is as follows.
Factory Settings
Y
N
Press
to enter the reset menu and select reset for factory settings.
Distance Adjust setting can be used to as an additive correction to the
measurement if the gauge output and true distance do not agree. When
LCD displays the number menu (menu number 4.3), press
enter the distance adjust menu setting. Display in LCD is as follows.
Press
to set the distance. Note that that the value should be
modified prior to changing the sign of the offset.
Distance Offset = Actual Distance to product - Measured Distance to
product
Distance Adjust
(Notes: This parameter is sign sensitive. Before committing the value
ensure the -/+ sign is correctly selected. This menu needs to be operated
by professionals)
Threshold setting is used to set the threshold limit of the effective echo.
The higher the threshold setting is, the higher the echo amplitude
required to trigger the level measurement. In turn, this eliminates small
signal clutter interference. Note that if the modified threshold value is
larger than the effective echo amplitude, no or false measurement might
result. The default range of echo threshold is 8 DB. See
the definition of this parameter.
Echo Threshold
SLN 700 SmartLine NCR Level Transmitter User's Manual
key to enter the reset function. Display in LCD
key to
Figure 5-2
for
Page 27